Daikin Thermal Store 300 AND 500 Litres
Product Features
Tank designed for connection with pressurised thermal solar system
Available in 300 and 500 liters
Large hot water storage tank to provide domestic hot water at any time
Heat loss is reduced to a minimum thanks to the high quality insulation
Space heating support possible (500l tank only)
Specifications Table for EKHWP-PB
EKHWP300PB EKHWP500PB
Heat exchanger Domestic hot water Tube material Stainless steel (DIN 1.4404) Stainless steel (DIN 1.4404)
Operating pressure bar 10.0 10.0
Internal coil volume l 27.8 29.0
Quantity 1 1
Charging Quantity 1 1
Operating pressure bar 6.0 6.0
Internal coil volume l 12.9 18.1
Auxiliary solar heating Internal coil volume l 3.9
Tube material Stainless steel (DIN 1.4404)
Operating pressure bar 3.0
Quantity 1
Dimensions Unit Width mm 595 790 Height Tank mm 1,646 1,658 Depth mm 615 790
Casing Material Impact resistant polypropylene Impact resistant polypropylene Colour Traffic white (RAL9016) / Dark grey (RAL7011) Traffic white (RAL9016) / Dark grey (RAL7011)
Tank Energy efficiency class B B
Maximum water temperature °C 85 85
Material Polypropylen Polypropylen
Water volume l 294 477
Weight Unit Empty kg 56 82 Full kg 350 559
Mounting Floor Floor
Notes (1) - Heatloss according to EN12897 (1) - Heatloss according to EN12897
(2) - TKW = 10°C/TWW = 40°C/TSP = 50°C (2) - TKW = 10°C/TWW = 40°C/TSP = 50°C
(3) - TKW = 10°C/TWW = 40°C/TSP = 60°C (3) - TKW = 10°C/TWW = 40°C/TSP = 60°C
(4) - TKW = 10°C/TWW = 40°C/TSP = 65°C (4) - TKW = 10°C/TWW = 40°C/TSP = 65°C
(5) - For tapping volume 140l -> 5820 Wh (bath) / 8kW heat pump
(5) - For tapping volume 140l -> 5820 Wh (bath) / 8kW heat pump
(6) - For tapping volume 90l -> 3660 Wh (bath) / 8kW heat pump (6) - For tapping volume 90l -> 3660 Wh (bath) / 8kW heat pump
(7) - For tapping volume 140l -> 5820 Wh (bath) / 16kW heat pump (7) - For tapping volume 140l -> 5820 Wh (bath) / 16kW heat pump
(8) - For tapping volume 90l -> 3660 Wh (bath) / 16kW heat pump (8) - For tapping volume 90l -> 3660 Wh (bath) / 16kW heat pump
(9) - Heat exchanger connected in parallel, TKW= 10°C/ TWW= 45°C/ TSP= 65°C/ Pload= 35kW/ Tflow= 80°C (9) - Heat exchanger connected in parallel, TKW= 10°C/ TWW= 45°C/ TSP= 65°C/ Pload= 35kW/ Tflow= 80°C
(10) - TKW= 10°C/ TWW= 45°C/ TSP= 65°C/ Pload= 35kW/ Tflow= 80°C (10) - TKW= 10°C/ TWW= 45°C/ TSP= 65°C/ Pload= 35kW/ Tflow= 80°C
Have a Trade Account? Click here to sign in to show discounted pricing.
Or if you think you're eligable for trade discount? Sign up here.
Products returned to us in a sellable condition will be credited subject to prior agreement and will incur a 25% restock charge.
Gas Spares and electrical items cannot be returned for credit.
If a product has failed within its warranty period, it will need to be sent to the manufacturer for testing, once the we have received credit from the manufacturer, we will then credit your account in full.
For more information please visit our returns policy here.